Abstract
This study provides an open-source dataset of the measured weather data, building indoor data, and system data under the different test settings. The test building is the two-story Flexible Research Platform building at the US Department of Energy’s Oak Ridge National Laboratory, in Oak Ridge, Tennessee. Four heating tests and three cooling tests were conducted. The 1-min interval of weather, building indoor data, and system data from each test setting are provided. Actual weather data were collected from a weather station installed on the roof. This paper describes information on the test building and installed sensors, data collection method, and data validation. The provided dataset can be employed to understand HVAC system conditions and building indoor conditions under different HVAC system operations and the performance of building envelope without HVAC system operation using free-floating test data. Additionally, it can be used for empirical validation of the building energy modelling engine.
Measurement(s) | temperature, humidity, energy, airflow rate, and solar radiation |
Technology Type(s) | Data logger, building automation system, and weather station |
Background & Summary
In 2021, commercial buildings were one of the main consumers of energy, accounting for 18% and 35% of total energy consumption and total electricity energy consumption in the United States1. Specifically, 40% of energy is consumed by HVAC systems2. Because HVAC system energy consumption is the largest portion of commercial building energy consumption, there are many ongoing efforts to reduce building energy consumption by implementing a high-efficiency HVAC system (e.g., energy recovery ventilator, demand-controlled ventilation, variable refrigerant flow)3,4,5 and HVAC system controls (e.g., model predictive control, adaptive predictive control, pattern recognition adaptive control, and transactive control)6,7,8,9.
Since experimental testing is time-consuming and difficult to gather high-quality data from10, most case studies use building simulation models. To ensure the reliability of the simulation results, the building simulation model needs to be calibrated or validated before it is used. Because of minimal field data, calibrating all scenarios with field data is difficult. Therefore, the base model is typically calibrated with the field data, and a case study is performed based on the calibrated base model11,12,13. Alternatively, a reference building energy simulation model (e.g., prototype buildings developed by the US Department of Energy14) can be used for the case study15,16,17,18.
Existing open-source datasets related to building energy consumption fall under the following two main categories: residential buildings19,20,21 and commercial buildings10,22,23. For residential buildings, Jacoby et al. provided single-family household data related to indoor conditions with occupancy behaviour19. Makonin et al. provided single-family household data in Canada20. Schlemminger et al. provided data on 38 single-family houses relating to the heat pump system in a 1-min intervals21. For commercial buildings, Schweiker et al. provided 4 years of outdoor, indoor, and energy data for an office building in 10-min intervals22. Agee et al. provided 2 years of energy use data in 1-h intervals, energy production data from a renewable energy system in daily intervals, weather data in daily intervals, and building air leakage data23. Luo et al. provided building datasets including indoor data in 1 min intervals, outdoor data in 15-min intervals, energy data in 15-min intervals, system data in 1-min intervals, and occupant data in 10-min intervals under two test settings (i.e., conventional rule-based control and model-predictive control)10.
Most previous open-source datasets have focused on indoor and energy use data under one test setting and have considered occupied buildings. There are currently no open-source datasets generated based on different HVAC system operations in an unoccupied building showing the impact of the HVAC system operations on the building.
Because of the absent historical open-source datasets that focus on HVAC system operation, the goals of this paper are to provide detailed weather data, indoor conditions, and HVAC system data under different HVAC system operations in multizone commercial building, including constant thermostat setpoint and thermostat setback schedule. In general, multizone field tests have many uncertainties in monitoring data mainly due to uncertain and untracked occupancy behaviour and associated operating schedule of the building. As utilizing this unique facility, whose occupancy can be controlled (e.g., emulated), the dataset can have limited uncertainties among different HVAC operation scenario, which can provide apples-to-apples comparison among each case (except different weather condition).
This dataset has the following unique features:
-
High quality, high-resolution one-minute interval data of the unoccupied multizone office building.
-
To reduce the uncertainty and fair comparison among different operating scenarios, no internal heat gain (e.g., people, lighting, and equipment) was emulated.
-
Dataset includes not only energy/power related data, but also indoor thermal condition data such as temperature, relative humidity per each zone.
-
Dataset includes on-site detailed weather data including outdoor temperature, RH, wind, solar, etc.
-
Provide the energy consumption data of each component in the installed HVAC system, including the compressors, condensers, supply fan, and variable air volume (VAV) boxes, and the airflow rates of the rooftop unit (RTU) and each VAV box.
The potential use cases for the dataset can be as followings:
-
Understanding the performance of building envelope without HVAC system operation using free-floating test data.
-
Develop a data driven or grey box model of the building to be used for advanced controls such as model predictive controls, and automatic fault detection and diagnosis (AFDD).
-
Develop and train machine learning (ML) models to predict the building and system behaviour.
-
Evaluate the weather impact on energy use for the target building – Performing sensitivity study on weather data.
-
Use for calibration of the building energy simulation model.
As an example, Im et al. used cooling season dataset to validate the EnergyPlus simulation model24.
Methods
Facility information
The two-story Flexible Research Platform (FRP-2) at the US Department of Energy’s Oak Ridge National Laboratory in Oak Ridge, Tennessee was selected as the test building. The building’s width and length are both 13.41 m, as shown in Fig. 1. Each floor has 5 conditioned zones (for a total of 10 conditioned zones), and an unconditioned staircase connects the floors. Floor to floor height of the first floor is 4.1 m, and floor to ceiling height is 2.7 m. On the second floor, floor to floor height is 4.2 m, and floor to ceiling height is 2.4 m. Table 1 lists the building construction information. The window to wall ratio of the FRP-2 building is 28%. No internal heat gain (e.g., people, lighting, equipment) was considered during the test to avoid uncertainties.
The RTU is as the main HVAC system for FRP-2. The direct expansion (DX) cooling coil and heating coil are installed in RTU. DX cooling coil consumes electrical energy and heating coil connects to the gas furnace. Each of the 10 conditioned zones has its own VAV box for reheating. The capacity of the RTU is 44 kW (12.5 ton) with a 9.6 energy efficiency rating.
Test settings
This study included heating and cooling season tests. There were 4 different test settings for the heating season—baseline, free-floating, night set-back, and pre-heating. The cooling season test included the following three test settings: baseline, free-floating, and night set-back. Each test period lasted around 1 week.
For the baseline test, setpoint temperature was constant throughout the day. The HVAC system was always switched on and operated to meet minimum VAV airflow when heating and cooling load was absent from the test building.
For the night set-back and pre-heating tests, the three HVAC system operation hours included occupied hours, unoccupied hours, and pre-heating hours. HVAC system operation during occupied hours was the same as the baseline test. During unoccupied hours, the HVAC system was switched off (i.e., 0 m3/s airflow) when the indoor air temperature was between the 15.6 °C (heating set point temperature) and 29.4 °C (cooling set point temperature) and switched on when indoor air temperature was lower than the set point temperatures. During pre-heating hours, HVAC operation was identical to the occupied hour operation except for the heating and cooling set point temperatures. The information on the test periods is provided in Table 2.
The test settings in the heating season are described in Table 3. For the pre-heating test, the HVAC system was switched off from 8 to 10 a.m. after the pre-heating from 5 to 8 a.m. The discharged air temperature set point for all scenarios, except for the free-floating test, was 13.9 °C.
The test settings in the cooling season are described in Table 4. The discharged air temperature set point for all scenarios, except for the free-floating test, was 12.8 °C.
Across all tests, some underlying test settings are as follows:
-
Windows and doors closed
-
Window blinds not used
-
No internal heat gain from lighting, equipment, or people during test periods
-
No outdoor air intake to the HVAC system
-
Static pressure fixed at 249 Pa
Data Records
The dataset is available at Figshare25. Figure 2 shows the sensor types and locations in the HVAC system. More than 500 sensors were installed in the test building, including zone temperature and relative humidity, supply and return air temperature, relative humidity, airflow rate, and power measurements. The field data were collected by the data logger (CR 3000) installed in FRP-2.
This dataset includes 16 comma-separated values (csv) files, 2 data description file, 7 weather data files, and 7 building data files, which means 1 weather data file and 1 building data file per test setting, as described in Table 5.
Weather data
Figure 3 shows the dedicated weather station installed on the roof of FRP-2. Weather data were collected every 30 seconds and automatically generated data every minute and hour. The weather data variables and units are described in Table 6.
Building data
Building data were collected every 30 seconds and automatically generated data every minute and hour. Data variables and units are described in Table 7. The indoor conditions, air temperature, relative humidity, and set point temperature are included in the provided dataset. The supply and return air temperature, relative humidity, and set point temperature are also included. Energy consumption of the compressor, condenser, VAV reheating, and fan are included, along with RTU fan and VAV airflow rate.
Technical Validation
The field dataset was divided into two subsections for technical validation. For the reliability of the sensor reading, the team confirmed the installed sensor accuracy, and for validation of each field dataset per test setting, field data analysis was performed.
Sensor accuracy
Table 8 describes the specifications of the installed sensors provided by the manufacturers. The quality of the dataset is reinforced by the sensors’ accuracy.
Data analysis
A representative day was selected for each test scenario for field data validation purposes. Since test scenarios cannot be performed all at once, a representative day was selected based on the outdoor air temperature.
Heating season testing
We selected representative days to validate the field dataset during the heating season. Figure 4a shows the outdoor air temperature pattern in each scenario. 6 March 2021, 8 January 2022, and 23 January 2022 were selected as representative days for the heating baseline test, night set-back test, and pre-heating test, respectively. Figure 4b shows the weighted averaged indoor air temperature pattern in each scenario. In the baseline test, the indoor air temperature was 21 °C. In the night set-back test, the indoor air temperature was around 21 °C during the occupied hours and it decreased during the unoccupied hours. In the pre-heating test, the heating set point temperature was 23.9 °C from 5 to 8 a.m., and the indoor air temperature increased until it reached 23.9 °C but decreased until it reached 21 °C after pre-heating.
During the free-floating test, the outdoor air temperature was higher than other heating test settings. Figure 5 shows the outdoor air temperature and weighted averaged indoor air temperature in free-floating test. 23 February 2021 was selected as a representative day—when temperature differences between minimum and maximum were the largest—to observe the weighted averaged indoor air temperature pattern. Because the HVAC system was switched off during the free-floating test, the weighted averaged indoor air temperature pattern was identical to the outdoor air temperature pattern.
Figure 6a,b show the RTU and VAV box energy consumption in each test scenario. The RTU was on and off frequently during the heating season. During the baseline test, the RTU was switched on all day because the HVAC system was also switched on all day. The RTU was never switched on during the free-floating test. During the night-setback test, the RTU was switched on during the occupied and unoccupied hours when the heating load occurred because RTU energy consumption included the RTU supply fan. During the pre-heating test, the RTU was switched on all day, except from 8 to 10 a.m., when the HVAC system was switched off after the pre-heating from 5 to 8 a.m.
The VAV boxes consumed energy all day during the baseline test. They consumed more energy during the night when the heating load was higher. The VAV boxes were not switched on for the free-floating test. For the night set-back test, the VAV boxes were switched off from 10 p.m. to 12 a.m. after the occupied hour; however, the VAV boxes were switched on from 12 a.m. because of dropping indoor air temperatures. The VAV boxes consumed more energy than during the baseline test from 7 to 9 a.m. to increase the indoor air temperature to the 21 °C heating set point temperature. During the pre-heating test, the VAV boxes consumed more energy from 5 to 8 a.m. because of the higher heating set point temperature (i.e., increased from 21 °C to 23.9 °C) for pre-heating purposes. The VAV boxes were switched off from 8 to 10 a.m. because the HVAC system was also switched off during these hours.
Cooling season testing
We selected representative days to validate the field dataset during the cooling season. Figure 7a shows the outdoor air temperature pattern in each scenario. 9 July 2021, 21 July 2021, and 31 July 2021 were selected as representative days for the cooling baseline test, free-floating test, and night set-back test, respectively. Figure 7b shows the weighted averaged indoor air temperature pattern in each scenario. In the baseline test, the indoor air temperature was almost constantly recorded at 21 °C. In the night set-back test, the indoor air temperature was around 22 °C during the occupied hours and 25 °C during the unoccupied hours. In the free-floating test, the indoor air temperature changed depending on the outdoor air temperature.
Figure 8a,b show the RTU and VAV box energy consumption from each test scenario. The HVAC system was switched off for the free-floating test, which means there was no RTU or VAV box energy consumption. For the night set-back test, the HVAC system was switched on during occupied hours and when the indoor air temperature was higher than 29.4 °C during unoccupied hours. Since indoor air temperature of the night set-back test was around 25 °C during unoccupied hours (Fig. 7b), the HVAC system was switched on when the indoor air temperature was higher than 25 °C during unoccupied hours. Since indoor air temperature was never higher than 25 °C during unoccupied hours, the HVAC system was not switched on until 7 a.m. During the baseline test, the HVAC system was switched on all day, and the RTU and VAV boxes were on all day. Since outdoor air temperature during day was higher than during the night, the VAV boxes consumed more energy during the day.
To explain why indoor air temperature was around 21 °C as opposed to 24 °C, which is the cooling set point temperature (Fig. 7b), We analysed the fan energy consumption supply airflow rate (Fig. 9a,b). Even if the cooling set point temperature was 24 °C for the cooling season test, the indoor air temperature was around 21 °C in both the baseline and night set-back tests. This is caused by the VAV box operation. Even when the indoor air temperature was within a comfortable range which is between the heating and cooling set point temperatures, the VAV box operated with a minimum airflow rate. Consequently, all conditioned zones received supply air with minimum airflow rates when the HVAC system was switched on. As an underlying test setting, the RTU supply air set point temperature was 12.7 °C; however, this set point was too low when the indoor air temperature is in a comfortable range. To increase the supply air temperature, the supply air was reheated by the VAV box. Thus, the indoor air temperatures of the baseline and night set-back tests were closer to the heating set point temperature (21 °C) and not the cooling set point temperature (24 °C). Because the VAV box operates to reheat supply air with minimal airflow rates, the VAV box consumes more energy at night (Fig. 8b). For these reasons, the RTU supply airflow rate was constant in the baseline tests. Since the RTU supply airflow rate was the same as the supply airflow rate from the 10 VAV boxes with no duct leakage, the RTU supply airflow rate was constant because each VAV box requested a constant minimal airflow rate.
Code availability
No code was used in the generation of this data. No code is required to access or analyse this dataset.
References
EIA (US Energy Information Administration). Monthly Energy Review, EIA (2021).
EIA (US Energy Information Administration). 2012 CBECS Survey Data - Consumption & Expenditures (2016).
Al-Waked, R., Mostafa, D.-B. & Nasif, M.-S. Performance of energy recovery ventilators under different climatic regions. Energy Efficiency 14, 8 (2021).
Delwati, M., Merema, B., Breesch, H., Helsen, L., & Sourbron, M. Impact of demand controlled ventilation on system performance and energy use. Energy and Buildings 174 (2018).
Lee, J., Im, P., & Song, Y. Field test and simulation evaluation of variable refrigerant flow systems performance. Energy and Buildings 158. IFAC-PapersOnLine 51 (2018).
Bird, M., Daveau, C., O’Dwyer, E., Acha, S., & Shah, N. Real-world implementation and cost of a cloud-based MPC retrofit for HVAC control systems in commercial buildings. Energy and Buildings 270 (2022).
Gholamzadehmir, M., Pero, C-D., Buffa, S., & Fedrizzi, R. Adaptive-predictive control strategy for HVAC systems in smart buildings – A review. Sustainable Cities and Society 63 (2020).
Gupta, S., Rao, V., & Nutter, B. Energy efficient control methods of HVAC systems for smart campus. 2018 IEEE Green Technologies Conference (2018).
Huang, S., Lian, J., Hao, H., & Katipamula, S. Transactive control design for commercial buildings to provide demand response. IFAC PapersOnLine 51–34 (2019).
Luo, N. et al. A three year dataset supporting research on building energy management and occupancy analytics. Scientific Data 9, 156 (2022).
Cai, M. et al. Impact of HVAC Set Point Adjustment on Energy Savings and Peak Load Reductions in Buildings”. 2018 IEEE International Smart Cities Conference (ISC2). (2018).
Chen, Y., Yang, C., Pan, X., & Yan, D. Design and operation optimization of multi-chiller plants based on energy performance simulation”. Energy and Buildings 222 (2020).
Fu, Q. et al. Optimal control method of HVAC based on multi-agent deep reinforcement learning. Energy and Buildings 270 (2022).
DOE (US Department of Energy). Commercial Prototype Building Models, Building Energy Codes Program (2022).
Papadopoulos, S., Kontokosta, C-E., Vlachokostas, A., & Azar, E. Rethinking HVAC temperature setpoints in commercial buildings: The potential for zero-cost energy savings and comfort improvement in different climates. Building and Environment 155 (2019).
Dehwah, A-H-A. & Krarti, M. Optimal controls of precooling strategies using switchable insulation systems for commercial buildings. Applied Energy 320 (2022).
Zhang, Y. et al. Energy consumption modelling of a passive hybrid system for office buildings in different climates. Energy 239 (2022).
Wang, L., Curcija, D., & Breshears, J. The energy saving potentials of zone-level membrane-based enthalpy recovery ventilators for VAV systems in commercial buildings. Energy and Buildings 109 (2015).
Jacoby, N., Tan, S.-Y., Henze, G. & Sarkar, S. A high-fidelity residential building occupancy detection dataset. Scientific Data 8, 280 (2021).
Makonin, S., Ellert, B., Bajic, I.-V. & Popowich, F. Electricity, water, and natural gas consumption of a residential house in Canada from 2012 to 2014. Scientific Data 3, 160037 (2016).
Schlemminger, M., Ohrdes, T., Schneider, E. & Knoop, M. Dataset on electrical single-family house and heat pump load profiles in Germany. Scientific Data 9, 56 (2022).
Schweiker, M., Kleber, M. & Wagner, A. Long-term monitoring data from a naturally ventilated office building. Scientific Data 6, 293 (2019).
Agee, P., Nikdel, L. & Roberts, S. A measured energy use, solar production, and building air leakage dataset for a zero energy commercial building. Scientific Data 8, 299 (2021).
Im, P., Joe, J., Bae, Y., & New, J-R. Empirical validation of building energy modeling for multi-zone commercial buildings in cooling season. Applied Energy, 261 (2020).
Im, P., Jung, S. & Yoon, Y. Datasets of a Multizone Office Building under Different HVAC System Operation Scenarios. figshare. https://doi.org/10.6084/m9.figshare.20520438.v3 (2022).
Acknowledgements
This material is based upon work supported by DOE’s Office of Science and BTO. This research used resources of ORNL’s Building Technologies Research and Integration (BTRIC), which is a DOE Office of Science User Facility. This work was funded by fieldwork proposal CEBT105 under DOE BTO activity nos. BT0302000 and BT0305000. This manuscript has been authored by UT-Battelle LLC under contract DEAC05-00OR22725 with DOE. The US government retains and the publisher, by accepting the article for publication, acknowledges that the US government retains a nonexclusive, paid-up, irrevocable, worldwide license to publish or reproduce the published form of this manuscript, or allow others to do so, for US government purposes.
Author information
Authors and Affiliations
Contributions
Yeobeom Yoon and Sungkyun Jung contributed equally to this work. Yeobeom Yoon analysed the field data, prepared open-source datasets, and helped write and edit the initial draft of the manuscript. Sungkyun Jung managed raw data collection, conducted field tests, and helped write and edit the initial draft of the manuscript. Piljae Im conducted field tests, supervised the research effort, and helped write and edit the initial draft of the manuscript. Anthony C Gehl conducted field tests and helped edit the initial draft of the manuscript. All co-authors read and approved the publication of the manuscript. Correspondence and requests for materials should be addressed to Piljae Im.
Corresponding author
Ethics declarations
Competing interests
The authors declare there are no competing interests for this study.
Additional information
Publisher’s note Springer Nature remains neutral with regard to jurisdictional claims in published maps and institutional affiliations.
Rights and permissions
Open Access This article is licensed under a Creative Commons Attribution 4.0 International License, which permits use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons license, and indicate if changes were made. The images or other third party material in this article are included in the article’s Creative Commons license, unless indicated otherwise in a credit line to the material. If material is not included in the article’s Creative Commons license and your intended use is not permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly from the copyright holder. To view a copy of this license, visit http://creativecommons.org/licenses/by/4.0/.
About this article
Cite this article
Yoon, Y., Jung, S., Im, P. et al. Datasets of a Multizone Office Building under Different HVAC System Operation Scenarios. Sci Data 9, 775 (2022). https://doi.org/10.1038/s41597-022-01858-6
Received:
Accepted:
Published:
DOI: https://doi.org/10.1038/s41597-022-01858-6